1 Introduction

With rapid urbanization, more and more urban rail transit systems are under construction or in planning; this phenomenon is especially common in fast-developing countries. As an important part of the urban rail transit system, metro stations have attracted significant attention from both the metro system managers and researchers. They are most concerned about how to ensure the normal operation of the metro station and the evacuation of the crowd in emergency conditions.

According to the previous statistics of historic accidents, fire is one of the biggest and serious threats to metro systems, with the metro stations included [1]. Once a fire breaks out in a metro station, the high temperature, toxic gas, and smoke will not only affect the structure of the station but also may cause a significant loss of life [2]. Death is usually caused by poisoning or hypoxia from smoke and toxic gases produced by fire, and the smoke will also reduce the visibility along the evacuee’s path, thus prolonging the exposure time to toxic gases [3].

The information of several significant fires that occurred in metro stations around the world is listed in Table 1. As can be seen from Table 1, fires that happen in metro stations can result in a large number of deaths and injuries. As for the reasons of the injuries and fatalities, exposure to smoke, toxic gas, and high temperature are the three main reasons according to the summary of historical fires [9, 10].

Table 1 Significant fires in metro stations around the world

Previous research related to fires that happen in metro stations has been carried out by researchers from all around the world. By using a heptane pool (heat release rate 1.5 MW) located in a subscale tunnel model, Blanchard et al. [11] revealed the relationship between the heat flux received by the ceiling and the critical velocity. Numerical simulation and field test was carried out by Zhu et al. (2017) to estimate the effect of different ventilation conditions under fire conditions of a metro tunnel, and the position with most unfavorable smoke conditions for passenger’s life safety was discussed as well [12]. Three full-scale model experiments were conducted in a unidirectional metro tunnel by Weng et al. [13]. By establishing a reduced-scale metro station model, Meng et al. [14] investigated the smoke temperature beneath the tunnel ceiling for a train on fire as it stopped at the side of a subway station platform. A reduced-scale subway station model was used by Giachetti et al. [15] to study smoke spreading, and the influence of the number of subway station openings and the ventilation volumetric flow rate were analyzed according to the data obtained by the model.

Due to the high costs of experimental tests, numerical modeling has also been used to study the fires that happen in metro stations. Computer software including Fire Dynamic Simulator (FDS), Fluent, Consolidated Fire and Smoke Transport (CFAST), and AIRPAK have been widely used for fire simulation. By using FDS, metro station fire simulations were carried out by Meng, N and Hu et al to study the effectiveness of different ventilation modes under the condition of fire that happens in a train that is stopped in a subway station (2014) [16]. FDS software was adopted by Zhao et al. (2016) to study the effects of different ventilation modes on the smoke spreading in a subway station with a unique structure after fire breaks out [17]. Yuan et al. [18] came up with an optimization method for the ventilation condition of a subway side platform by using the software AIRPAK. Wang et al. [19] studied the smoke spread of a fire occurring on the subway platform by using software Fluent and FDS. In general, numerical simulation has become more and more popular for its low cost and efficiency.

As identified above, a lot of research related to the fire that happed in the metro station has been carried out. However, a comparison of fires that happen in metro stations with different structures and layouts has not been reported. Understanding how the toxic and harmful substances produced by fire spread in metro stations with different structures can be helpful for the structure design of metro stations to be constructed. Besides, fire simulation software has been widely used for research for its low cost and accuracy. Fire models based on metro stations with typical structures used in the metro system of Washington, D.C., and Guangzhou Metro are established by using PyroSim, a widely used fire simulation software. The spread characteristics of the toxic gases produced by the combustion will be compared and discussed. At last, the more appropriate structure for metro stations to be built is proposed when other factors like construction cost are also taken into account.

1.1 Structures of Typical Metro Stations

1.2 Typical Station Structure of Washington, D.C., Metro System

The metro system of Washington, D.C., was opened to the public in 1976. The metro system of Washington, D.C., now has 91 stations, which are connected by 6 lines with a total length of 188.3km. Most metro stations in the suburban area of Washington, D.C., are elevated stations, while underground stations are more common in urban areas. Figure 1 shows a common structure widely adopted in the metro system of Washington, D.C. The underground stations of the metro system of Washington, D.C. usually have a high and arched ceiling, i.e., a “high-dome” structure, which is quite different from the common structure of metro stations in other cities. The escalator and staircase at the two ends of the platform are used to connect the platform with a smaller terrace, where tickets can be purchased. The terrace acts as the station hall of other metro systems, but it is smaller than a regular station hall. Most underground metro stations in Washington, D.C., use the “island-style” platform as shown in Figure 1.

Figure 1
figure 1

“High-dome” structure widely used in stations of the metro system of Washington, D.C.

1.3 Typical Station Structure of Guangzhou Metro System

The first rail line of Guangzhou Metro began to operate on 28 June, 1997. Guangzhou Metro already has 14 rail lines with a total length of 478km after developing for more than 20 years. There are 257 metro stations connected by these 14 rail lines. Just like stations in Washington, D.C., most metro stations located in the urban area of Guangzhou are underground stations. The “two-layer” structure shown in Figure 2 is widely used for underground metro stations in Guangzhou.

Figure 2
figure 2

“Two-layer structures” most widely adopted in underground stations in Guangzhou

As shown in Figure 2, metro stations with “two-layer” structures are composed of two layers; they are the station hall layer and the platform layer. For underground metro stations, the station hall layer is usually the first layer underground, and the station hall layer is connected with ground/streets by exit/entrance. The platform layer is below the station hall layer, and it is typically the second layer underground. Usually, the station hall layer and platform layer are connected by several escalators, elevators and/or staircases.

The typical platform layer for an underground metro station in Guangzhou is shown in Figure 3. The “island-style” platform is most common in the stations of Guangzhou metro, and the platform screen doors (PSD) are installed on both edges of the platform. Ventilation systems are installed on the ceiling of the platform layer, which is used for daily air renewal and smokes exhaust under fire conditions. As shown in Figure 3, this kind of metro station has a “flat ceiling”, as shown in Figure 3, which is quite different from the “high-dome” structure widely used in Washington, D.C.

Figure 3
figure 3

Typical metro station with “flat ceiling” in Guangzhou (platform layer)

2 Metro Station Fire Simulation Model

2.1 Simulation Software

FDS has been used by researchers to study fires in a variety of buildings and occupancies, including high-rise buildings [20], cinemas [21], high-speed trains [22], and metro stations [23]. PyroSim is a simulation software for fire dynamics with human–computer interaction and a graphical user interface. The software can quickly and conveniently build models and directly present the calculated results in graphic and other visual forms, which has been widely used. Thus, PyroSim was selected to establish fire models for typical metro stations of Washington, D.C., and Guangzhou in this article.

2.2 Dimension and Simulation Models of the two Typical Metro Stations

When establishing the fire model of a typical Guangzhou Metro station, the “flat ceiling” structure shown in Figure 3 was selected. The dimension of the Guangzhou Metro station used to establish the model is shown in Figure 4. The platform of this station is an “island-style” platform with a width of 12 m. There are two 3.3-m-wide track areas on both sides of the platform. The platform layer is 120 m in length, 4.7 m in height, 18.6 m in width, and 120 m in length, respectively. Platform screening doors (PSD) are installed on the two edges of the platform.

Figure 4
figure 4

The dimension of the typical metro station in Guangzhou used to establish the fire simulation model (cross section)

The dimension of the typical station in Washington, D.C., used to establish the fire simulation model is illustrated in Figure 5. As shown in Figure 5, the platform is “island-style”, and there are track areas with 3.3 m width on both sides of the platform. The platform is 0.98 m in height, 12 m in width, and 120 m in length. The distance between the surface of the platform (ground) and the highest point of the tunnel is 8.45 m. It means the clearance of the platform layer is 8.45 m.

Figure 5
figure 5

The dimension of the fire simulation model based on the typical station in the metro system of Washington, D.C. (cross section)

Table 2 shows the information about the mesh information of fire model established based on typical metro station of Guangzhou and Washington, D.C. These two models will be called Guangzhou model and Washington model for short in the latter part of this article. To ensure the accuracy of the simulation results, different cell sizes were applied when meshing the models and the results obtained from these models are compared. When some mesh sizes are adopted, the model cannot complete the calculation, i.e., non-convergence problem, this proves that these kinds of mesh sizes are inadaptable. Also, finer meshes will lead to a long calculation time.

Table 2 Mesh information of the two typical stations' fire dynamic simulation models

Reasonable mesh size should ensure the accuracy of the calculation results and the calculation time should not be too long. After multiple computational attempts and comparisons, the author found reasonable results can be obtained by applying cell size presented in Table 2 to the Guangzhou model and the Washington model, and the calculation time is less than 10 h. Besides, after the models have been meshed, the Mesh Alignment Test Function provided by PyroSim is applied for the mesh verification to ensure the models are well meshed.

2.3 Factors of Fire

Fire sources with different materials, different fuels, and different factors such as heat release rate will have a significant impact on the development of fire and the generation of smoke and poisonous gases. When establishing a fire model, it’s very important to determine the right fuel, material, and heat release rate for the fire source to be used in the fire scenario. According to the reports, most historical fires that happened in metro stations are caused by luggage or other items, for flame-resistant material are mandatorily used for the station decoration and all other equipment to be used in a metro station according to laws or regulations [24].

The heat release rate of fire that happened in crowded places ranges from 2.0 to 2.5 MW [25]. Thus, fires with a heat release rate of 2.5 MW which is considered as the most unfavorable condition are set in both the Guangzhou metro station model and the Washington metro station model.

After the heat release rate of the fire source is determined, the growth model is to be determined. According to the report of Gunnar Heskestad et al. (1989), the heat release rate will increase with time during the first stage after the fire begins. The growth of heat release rate in this stage can be illustrated by Eq. (1) [26].

$$\text{HRR}= \alpha t^2$$
(1)

In the equation, HRR is heat release rate, kW; α, fire growth factor, kW/s2; t, time after the fire breaks out, s.

In this article, the t2 model (shown in Figure 6) which is a non-steady fire growth mode is selected when establishing the fire models. After the heat release rate reaches the maximum value HRRmax, the growth of the heat release rate will then enter the second stage. The heat release rate will keep at the maximum value in the second state as shown in Figure 6.

Figure 6
figure 6

The increase of HRR in the t2 fire model

Different fire sources have different growth rates of heat release rate, which can be illustrated by fire growth factor α. The corresponding fire growth factor of different fire growth rates can be found in Table 3. The growth rates of the fire used in the Guangzhou model and Washington model are assumed to be ultra-fast, and the value of fire growth factor α will be 0.1878 according to Table 3.

Table 3 Different fire growth factors corresponding to the different fire growth rates

From what has been discussed above, the heat release rates of fires used in the models are 2.5 MW, with a fire growth factor of 0.1878. By Eq. (1), the heat release rate of the fire in the Guangzhou model and Washington model will increase during the first 115 s after the fire begins and then enter the steady stage. In both fire models for Guangzhou Metro station and Washington, D.C., Metro station, materials of the fire source are set to be polyurethane, whose composition is listed in Table 4.

Table 4 The material composition of polyurethane used in fire models

2.4 Fire Scenarios

When a fire happens in a real metro station, the location of the fire is random and can be anywhere in the station. Fires in both the Guangzhou model and the Washington model are set to happen on the platform. As for the location of the fire, fires that happen in the center of the platform and at the end of the platform are considered when establishing fire models for Guangzhou and Washington, D.C., Metro stations. Figure 7 illustrates the fire locations on the platform of metro station models.

Figure 7
figure 7

Locations of the fires on the platform of Guangzhou model and Washington model

2.5 Environmental Settings

Both the Guangzhou model and Washington model are established based on their typical underground metro stations, and there is typically limited airflow in relatively confined spaces like underground metro stations. Thus, it is assumed that there is no airflow in the metro station of the Guangzhou model and Washington model. Also, the original temperature in the metro station of both models was set to be 20 °C for the stations are equipped with air conditioning systems. According to Jeon et al. (2011), the visibility in a metro station in a normal building is usually greater than 20 m when lighting is on and regarding evacuee’s vision [27]. The maximum visibility on the platforms of both models is set at 30 m in the metro station of both models. For the models of the station in Guangzhou, the platform screening doors are set to be closed during the simulation calculation process.

2.6 Established Model

The established models based on typical metro stations in Guangzhou and Washington, D.C., are shown in Figures 8 and 9, respectively. The ceilings of the two models are fully or partially removed for a better view of the inner structure of the station. The fire source (marked as a red square) is located in the center of the platform.

Figure 8
figure 8

The established model based on the typical metro station in Guangzhou (flat ceiling removed)

Figure 9
figure 9

The established model based on the typical metro station in Washington, D.C. (high-dome ceiling partially removed)

The established model based on the typical structure of Washington, D.C., Metro station is the same as the model based on the typical structure of Guangzhou Metro station except for the platform ceiling, the former metro station model has a platform structure shown in Figures 1 and 5, in the shape of “high dome,” while the Guangzhou model has a platform layer structure shown in Figures 3 and 4, in the shape of “flat ceiling”.

2.7 Location of the Monitoring Devices

2.7.1 Smoke Layer Height Detector

Smoke layer height detectors are installed in the established models. The location of the smoke layer height detectors is shown in Figure 10. Eight smoke layer height detectors are installed at the same locations in the models based on the station of the metro system of Washington, D.C., and Guangzhou Metro station. The serial numbers of these eight smoke layer height detectors are shown in Figure 10. The smoke height change at these locations can be monitored and recorded during the entire simulation process.

Figure 10
figure 10

Locations of the two smoke layer height detectors (not to scale)

2.7.2 Thermocouples

Eight thermocouples are installed 1.7 m high above the platform in both Guangzhou models and Washington models. The locations of these thermocouples are shown in Figure 11. The thermocouples provide data related to the temperature change throughout the simulation period.

Figure 11
figure 11

Locations of the thermocouples (not to scale)

2.7.3 Temperature and Visibility Slices

Slices in PyroSim allow contours of temperature and visibility to be exported as outputs of the simulation. To make a comparison between the models of the different metro stations, temperature and visibility slices were added to both models. The temperature slices were installed at the safety smoke heights of the two models, and they are 1.945 m in the Guangzhou model and 1.8 m in the Washington, D.C., model. The visibility slices were installed 1.6 m above the floor of the platform in both models, for the average height of women in most countries is around 1.6 m according to Wikipedia [28].

3 Results and Discussion

3.1 Smoke Height Change

In the event of a fire occurring in a relatively enclosed space, the smoke generated by the fire will first accumulate at the top of the space and gradually decrease with time [29]. Passengers can be safely evacuated only under the condition that the smoke height is always above the safety height during the whole evacuation process. Otherwise, passengers in the evacuation process will be more or less affected by the smoke. Equation (2) proposed by Shi et al. (2008) can be used for the calculation of the safety height of smoke [30].

$$\text{Hs} = 1.6+0.1H$$
(2)

In the equation, Hs is safety height of smoke (m). H, interior space height of the building where fire happens, m, for example, the height of a classroom or hall.

The height of the platform layer (clearances) in the Guangzhou models is 3.45 m, so the safety height of smoke on each platform is 1.945 m according to Eq. (2). However, the International Building Code (2018), which is widely adopted in the USA, suggests the smoke layer must not descend below 1.8 m above the highest walking surface [31]. Thus, the safety height of smoke for the metro station models of Washington, D.C is set as 1.8 m.

Figures 12 and 13 illustrate the smoke height change during 0–360 s in the Guangzhou model and Washington model, respectively. As shown in Figure 12a, b, the smoke height varies between 2.75 and 3.45 m when the fire location is in the platform center, while the smoke height varies between 2.55 and 3.45 m when the fire location is at the end of the platform. The lowest smoke height to the safe height of smoke (1.95 m) is about 0.8 m and 0.6 m, respectively.

Figure 12
figure 12

Smoke height change of Guangzhou model

Figure 13
figure 13

Smoke height change of Washington model

A similar result is observed for the model based on the typical Washington, D.C., Metro station. As shown in Figure 13, the lowest smoke heights are both around 7.85 m when the fire is located in the platform center and at the end of the platform. The lowest smoke height to safe height of smoke 1.8 m is about 6.15 m when the fire is on the platform center, while its 6.2 m when the fire is at the end of the platform.

It can be seen that when the same fire breaks out in metro stations of Guangzhou and Washington, D.C., it takes more time for the smoke height to drop below the safe smoke height in the Washington, D.C., station. This means passengers in Washington, D.C., Metro stations will have more time to escape before the smoke height becomes too low under the same fire condition. These simulations did not include the operation of the smoke exhaust system which could result in different available safe evacuation times. To make the smoke height drop slower in the typical metro station in Guangzhou, more powerful smoke exhaust equipment should be installed.

3.2 Temperature Change

The monitored temperature change of the thermocouples during 0–360 s in the Guangzhou model and Washington model is shown in Figures 14 and 15, respectively. The highest temperature monitored in the Guangzhou model is about 43 °C when the fire is located in the platform center, while the highest temperature is about 49 °C when the fire is located at the end of the platform. It means the maximum temperature increment monitored is 23–29 °C in the set scenario of the Guangzhou model.

Figure 14
figure 14

The temperature change of the Guangzhou model

Figure 15
figure 15

The temperature change of the Washington model

As can be seen from Figure 15, the temperature of the thermocouples in the Washington model shows a rising trend during the whole calculation process. The highest temperature monitored in the condition fire locates in the platform center is about 29 °C, while the highest temperature is about 28.5 °C when the fire is located on the end of the platform. The maximum temperature increment monitored is 8.5–9 °C, which is much lower than that in the Guangzhou model.

Figure 16 illustrates the temperature on the slices 1.8 m above the platform floor in the Guangzhou model at the time 360 s after the fire begins. When the fire is located in the platform center of Guangzhou model, the highest temperature 40 °C appears in the areas of the platform center and the two ends of the platform. When the fire is located at the end of the platform, the highest temperature close to 50 °C appears at the end of the platform where the fire is located.

Figure 16
figure 16

Temperature slice 1.8 m above the platform floor at 360 s of Guangzhou model (unit: °C)

Figure 17 shows the temperature on the slice 1.945 m above the platform floor at 360 s after the fire breaks out in the station of Washington model. It shows the temperature in most areas of the platform is approximately 22–28 °C when the fire is located in the platform center, while the temperature ranges between 23 and 30 °C when the fire is located at the end of the platform.

Figure 17
figure 17

Temperature slice 1.945 m above the platform floor at 360 s of Washington model (unit: °C)

In general, the temperature in the station of Guangzhou model is much higher than that in the station of Washington model. This is because the room of the station of Washington model is much bigger than the station of Guangzhou model, it will need more heat to raise the temperature. As discussed before, lower temperatures will benefit the evacuation of passengers. It indicates that the metro station with a “high-dome” structure like the typical station in Washington can provide a safer evacuation environment when fires with the same scale break out.

3.3 Visibility Change

To ensure that evacuation routes can be seen under fire conditions, evacuation guide signs are typically installed in metro stations. In the event of a fire, the visibility in a metro station will be reduced by smoke. According to the Chinese Code for the Design of Metro System (GB 50157-2013), visibility of 10 m should be guaranteed during a fire that happens in a metro station. Figure 18 and Figure 19 illustrate the visibility on the slices 1.6 m above the platform floor at 180 s and 360 s after fire breaks out in the Guangzhou model.

Figure 18.
figure 18

Visibility slice 1.6 m above the platform floor at 180 s of Guangzhou model (unit: m)

Figure 19
figure 19

Visibility slice 1.6 m above the platform floor at 360 s of Guangzhou model (unit: m)

Figure 18 shows that when the fire breaks out in the platform center or at the end of the platform, the visibilities 1.6 m above the two sides of the platform floor at 180 s are both 1.0–10 m, which is well below the requirement of 10 m visibility. It can be seen from Figure 18a that the visibility at the two ends of the platform is much lower than the visibility in the center area. This is caused by the “ceiling effect”, the smoke will gather at the ceiling first and generally spread in the direction to the two ends of the platform after the smoke reaches the two ends of the platform, and more smoke will accumulate at the area above the end of the platform, thus making the visibility at the two ends of the platform very low, while when the fire is located at the end of the platform, the visibility is lower in the part of the platform which is close to the fire, as shown in Figure 18b.

As shown in Figure 19, the visibilities of all areas 1.6 m above the platform at 360 s after fire breaks out are approximately 1.0 m no matter the fire is located in the platform center or at the ends of the platform in the Guangzhou model.

Figures 20 and 21 show the visibility on the slices 1.6 m above the platform floor 180 s and 360 s after the fire starts of the Washington, D.C., model. Figure 20 shows the visibility at the height 1.6 m above the platform at 180 s is about 29 m in most areas of the platform when the fire is located in the platform center, while it is about 28.5 m when the fire is located at the end of the platform.

Figure 20
figure 20

Visibility slice 1.6 m above the platform floor at 180 s of Washington model (unit: m)

Figure 21
figure 21

Visibility slice 1.6 m above the platform floor at 360 s of Washington model (unit: m)

Figure 21 shows the visibility 1.6 m above the platform floor 360 s after the fire breaks out. Most areas of the platform have visibility of approximately 4–14 m as shown in Figure 21a when the fire is located in the platform center. When the fire is located at the end of the platform, the visibility at the platform in most areas is 1.5–13.5 m except the areas close to the fire.

The visibility decreased slower in the model based on the Washington, D.C., Metro station. At 180 s after the fire starts, the visibility in most areas of the Guangzhou model is among 1.0–10 m, while the visibility in most areas of the Washington, D.C., model is around 29 m or 28.5 m depending on the fire location. At 360 s after fire breaks out, the visibility in most areas of the Guangzhou model is quite low, approximately 1 m in most areas, while the visibility in most areas of the Washington, D.C., model is approximately 4.0–14 m or 1.5–13.5 m which depends on the fire location. Thus, passengers in the station with higher clearance can have more available time to evacuate before conditions become untenable.

4 Conclusions

Simulation models of fires on the platform of metro stations in Guangzhou and Washington, D.C., were studied. The two metro stations used for the scenarios have typical structures which are widely used in the metro system of Guangzhou and Washington, D.C. Results listed below are obtained by the simulation analysis:

  1. 1.

    The lowest smoke heights monitored in the Guangzhou model are 0.6 m (fire at the platform end) and 0.8 m (fire in the platform center) above the safe smoke height at 360 s after the fire breaks out, while it is 6.15 m (fire in the platform center) and 6.2 m (fire at the platform end) above the smoke height in the Washington model. It indicates that the time required for the smoke layer to descend in the lower ceiling case was nonlinear to the difference in ceiling height; the smoke layer descended faster than for the high ceiling condition.

  2. 2.

    The temperature in the platform layer of the Guangzhou model increases more quickly than that in the Washington, D.C., model after fire breaks out. The temperature increment in the Guangzhou model is 23 °C (fire in the platform center) to 29 °C (fire at the platform end) at 360 s after the fire breaks out, while the temperature increment in the same period in the Washington model is 8.5 °C (fire at the platform end) to 9 °C (fire in the platform center).

  3. 3.

    In the same fire condition, the visibility decreases slower in the Washington, D.C., model. The visibility of most areas on the platform of the Guangzhou model is about 1 m no matter the fire is in the platform center or at the platform end at 360 s after the fire begins, while in the Washington model, the visibility is 4–14 m (fire at the platform end) to 1.5–13.5 m (fire in the platform center) at the same moment.

As discussed above, the environment is worse when the fire happens at the end of the platform than that when the fire happens in the platform center of the Guangzhou model, while the fire location has fewer impacts on the smoke height, temperature, and visibility in the Washington model. A metro station with higher clearance can provide a safer evacuation environment when a fire breaks out. While the metro station with a higher ceiling provides more available safe egress time, higher ceilings may not always be the best option. Underground stations with higher clearances will require higher construction costs. The right construction structure of a metro station should also consider the cost, the geology, and the other related factors. If it is not feasible to build underground stations with higher clearance, other auxiliary measures, such as smoke exhaust systems, should be added to prolong the evacuation time of passengers.