The ductility performance of concrete using glass fiber mesh in beam specimens

  • Aylin Özodabaş EMAIL logo
From the journal Applied Rheology

Abstract

It is known that concrete with high ductility reduces fatalities because it absorbs more energy during an earthquake. The aim of this study is to increase the ductility of concrete by using glass fiber mesh (GFM) left over from the use of plaster in structures and to support sustainability by reusing waste materials in concrete. Another aim is to contribute to the economy by using waste fibers instead of expensive fibers such as carbon and polypropylene in concrete. Two types of concrete were used: class C25 concrete and self-compacting concrete. The specified number of GFM materials was cut into 3 cm wide pieces and placed in 10 cm × 10 cm × 50 cm concrete beam specimens in varying numbers. It was found that the flexural values of the obtained specimens gave slightly better results than the prepared reference specimen. In addition, the increasing stress zones in the beams were visualized using the ANSYS software.

1 Introduction

The main disadvantage of concrete is that concrete has low tensile strength and is less resistant to deformation [1,2] Different types of fibers are used to improve the flexural strength, fatigue resistance, and impact resistance of cementitious composites [3].

The application of rubberized concrete in earthquake zones is of great importance. The concrete beams incorporating waste rubber exhibited a 23.47% enhancement in ductility when contrasted with the control beam [4]. Over the past 10 years, efforts have been made to introduce ductility to concrete, with fiber-reinforced concrete being a notable approach [5]. To obtain a ductile beam, it depends on some parameters of the concrete class or fiber additions. Furthermore, as the quantity of jute fabrics was raised, the ductility of the beam specimens correspondingly increased [6]. Textiles and clothing are among our most important necessities of life. The textile and fashion industries have been forced to develop and put into practice ecologically friendly waste management and disposal techniques as a result of the growing environmental issues connected to the massive amounts of textile waste that are dumped in landfills. The textile sector is recognized as the second most significant source of industrial pollution. It contributes to 10% of worldwide carbon emissions and 20% of global wastewater [7]. Synthetic petroleum-based textiles in particular pose a major threat to environmental pollution. Unfortunately, their use and therefore production has increased in recent years [8]. Numerous components from non-biodegradable building waste will remain in the environment for hundreds or even thousands of years, contributing to environmental problems [9,10]. It is important to recycle plastic-containing waste or use it as a fiber in concrete.

It was found that concrete with textile or synthetic fibers has a higher elongation at break than PC concrete [11,12]. Another important condition is to reduce the weight of engineering structures as much as possible [13,14]. This type of building material is lighter than steel reinforcements and does not have disadvantages such as corrosion. Concrete is a kind of material that it is reinforced with fibers to increase its ductility [1518]. Furthermore, the fibers increase the ductility of the concrete and contribute positively to its waterproofness [19]. In a study, it was shown that by reusing waste rope fibers in concrete, the compressive strength of concrete increased by up to 22% and the flexural strength increased by 4.3% [20]. Figure 1 shows the share of textiles consumed worldwide in 2021. More and more synthetic textiles are being used. In this case, there is an increasing.

Figure 1 
               Rates of textiles consumed in the world in 2021 [21].
Figure 1

Rates of textiles consumed in the world in 2021 [21].

Fiber-reinforced polymers (FRP) are used in many industries because of their excellent mechanical properties and durability. This means that more and more FRP waste has to be processed in production. Conventional FRP composites are usually thermoset and non-biodegradable and pose a significant risk to the environment if they are not properly disposed of at the end of their life [13]. For this reason, the waste from FRP composites should be used in concrete or alternative recyclable materials should be used. Carbon fibers used in fabric-reinforced concrete matrix (FRCM) systems have been used [2225]. In lieu of these products derived from petroleum, textile waste was employed in the samples of the beams. The use of FRP created a new composite system known as FRCM or textile-reinforced mortar [2632].

Experimental and theoretical research on FRCM composites is still very limited compared to the number of studies on FRP systems [3335]. The addition of various polypropylene fabrics to the concrete significantly increased the freeze–thaw resistance [36]. Polymer fabric-reinforced cemented matrix concretes increased their resistance to cracking by over 30% [37]. The flexural strength of basalt textile-reinforced concrete specimens was noted to enhance as the number of textile layers increased [38].

The addition of fiber to concrete contributes to an improvement in energy absorption capacity as well as durability, increasing the strength of the structure and its resistance to fire [39]. The drying shrinkage and mechanical and rheological properties [40] of concrete have undergone enhancement by the use of natural fibers [4144]. In particular, short fibers were used in order not to adversely affect the rheological properties of concrete [45]. The production of synthetic fibers requires high energy consumption and will lead to significant environmental issues. Environmental concerns and industrial pollution have driven the engineering industry to seek fiber alternatives beyond synthetic and steel fibers. Readily available, biodegradable, cost-effective, and non-toxic natural fibers are seen as the best possible alternatives [46]. Adding natural fibers to concrete can increase impact resistance, while excessive fiber addition can lead to the deterioration of material properties [47]. As the workability of concrete decreases due to the use of fibers, problems arise with the concrete mix and its placement in the mold. The use of self-compacting concrete (SCC) avoids such problems [4851].

It is well known that the remaining parts of GFM used in construction pollute the environment as waste. For this reason, in this study, by using these GFM in concrete, it is possible to increase the flexural strength of concrete partially and to contribute to environmental cleaning by evaluating this waste material. Since the GFM was in fabric form, the beam was placed inside the samples to form a layer during concrete pouring. It was thought that it would increase the adhesion due to its mesh structure and increase the ductility because it acts as a fiber.

2 Experimental details

2.1 Specimen design

The dimensions of the manufactured beam samples were 10 cm × 10 cm × 50 cm. The GFM used in the manufactured specimens was attached in two stages. In the first specimens, the fibers were placed on the 1/3 level of the concrete beam, and in the others on both the 1/3 and 2/3 levels. Additionally, two fibers were used in each layer of the specified samples, while three fibers were used in each layer of the other samples. Each waste GFM was cut 3 cm wide. The fibers were inserted straight and diagonally into the test specimens (Figure 2). The fibers were positioned within the plane adjacent to the lower region, which constitutes the tensile area of the specimens. Figure 3 illustrates the experimental study’s phases in a schematic manner.

Figure 2 
                  Placing GFM diagonally or straight into concrete beams.
Figure 2

Placing GFM diagonally or straight into concrete beams.

Figure 3 
                  Levels of experimental study.
Figure 3

Levels of experimental study.

2.2 Materials

In plaster mesh, produced according to DIN ISO 13934-1, the tensile strength should be at least (N/50) and under standard conditions, it should be 1,600 N for warp and 1,900 N for weft. CEM I 42.5R Portland cement is used. A super-plasticizer, a product of the company SIKA, was used for the production of the SCC.

2.3 Test methods

Flexural tests were performed in line with TS EN 12390-5 standards, and Figure 4 depicts the results of the experimental investigation. Testing for durability in sulfated waters was done in accordance with ASTM C1012 guidelines.

Figure 4 
                  Flexural test on the sample.
Figure 4

Flexural test on the sample.

3 Results and discussion

3.1 Flexural test

As can be seen in Figure 5, while the fibers in C25 concrete specimens outperformed the reference specimen, the flexural strength values obtained from SCC produced slightly better results. In both forms of concrete, it is conceivable to say that the flexural strength values produce better results as the number of fibers grows. It is clear from Figure 5 that fibers in the cross position perform worse than fibers in the straight position.

Figure 5 
                  28-Day flexural strength tests of GFM in C25 and SCC concrete specimens.
Figure 5

28-Day flexural strength tests of GFM in C25 and SCC concrete specimens.

The fracture mode of the beam switched from brittle fracture to ductile fracture as the number of fibers increased. Analysis of the cracking pattern revealed that the ductile direction of breaking was increased in fiberglass beams. Since the GFM helps to avoid cracks, the presence of fiber reduces the shear stress in the beams.

The flexural strength values of the GFM-containing C25 samples were lower than the SCC samples. The reason for this is thought to change the position of the fibers in the mold with the vibration applied to the C25 concrete. SCC had the best value for flexural strength; the sample with 4 fibers measured 7.82 MPa, compared to 5.44 MPa for the reference sample. The flexural strengths of samples containing 4 fibers have shown an increase of approximately 43% compared to the reference sample. The fiber-containing beams in this instance were roughly 1.5 times more numerous than the reference sample. The fibers placed in the cross position gave lower values in C25 concretes than those placed in the straight position.

In previous studies, fibers of short lengths were directly added to the mixture mortar in specific proportions without being placed throughout the specimen, and their toughness and ductility were examined. During an earthquake, concrete’s brittle fracture poses a serious risk to human life. For this reason in our investigation, GFM is used along the beam specimen to try to offer ductile fracture by minimizing sudden fracture and to boost the load-absorbing capacity of the concrete against flexural forces. Previous research has shown that fiber utilization promotes ductility, and Figure 6 even shows that long fibers can withstand more stress than short fibers [5254].

Figure 6 
                  Mechanism of different sizes of fiber reinforcement [55].
Figure 6

Mechanism of different sizes of fiber reinforcement [55].

Figure 7 depicts the deformation zones discovered using the finite element method (FEM) analysis of concrete samples with GFM that are 28 days old. It can be shown that the C25 and SCC samples have superior deformation capacities than the reference samples. In a similar study, beams using steel-polypropylene fibers in short form exhibited a 17% increase in cracking load compared to concrete beams without fibers [56].

Figure 7 
                  GFM 28-day specimens FEM analysis (2C–4C: cross position, 2D–4D: straight position, and W: whole).
Figure 7

GFM 28-day specimens FEM analysis (2C–4C: cross position, 2D–4D: straight position, and W: whole).

3.2 90-Day flexural test

As shown in Figure 8, the results are consistent and the best flexural strength values were obtained from SCC specimens placed in a flat position. In another study, it improves quality control by reducing or eliminating traditional reinforcement and simplifying reinforcement details and placement. Combining fiber and SCC also supports sustainability [57].

Figure 8 
                  90-Day flexural strength tests of GFM in C25 and SCC concrete specimens.
Figure 8

90-Day flexural strength tests of GFM in C25 and SCC concrete specimens.

3.3 Durability tests in sulfated waters

In Figures 9 and 10, the flexural strength of specimens immersed in a 5% Na2SO4 solution for 3 months exhibited a notable decrease when compared to the specimens stored in water for 90 days. In addition, since the flexural values of the reference specimens and the fibrous specimens were very close to each other, it was observed that the fibers did not have a positive effect in sulfated environments. In this case, the fiberglass mesh is considered to dissolve in sulfated water. Similar strength values were seen in both groups held in sulfated water, even though the water strength of the SCC samples rose slightly over time compared to the C25 concrete samples.

Figure 9 
                  C25 specimens kept in sulfated water for 90 days.
Figure 9

C25 specimens kept in sulfated water for 90 days.

Figure 10 
                  SCC specimens kept in sulfated water for 90 days.
Figure 10

SCC specimens kept in sulfated water for 90 days.

In Figure 11, in C25 and SCCs immersed in sulfate waters, the straight or cross position of the fibers did not make much difference in the flexural values. Because it supports the idea that the fibers melt and lose their effectiveness in both groups.

Figure 11 
                  Flexural strength values for 90 days in sulfated water.
Figure 11

Flexural strength values for 90 days in sulfated water.

4 Conclusion

  • Among the 28-day C25 concrete specimens, they have the highest flexural strength value of 5.74 MPa, they are 4-fiber, that is, 2-level and flat-positioned specimens with 2 fibers at each level.

  • Within the set of specimens utilizing 28-day SCC, the specimen with the highest flexural strength value was achieved by the configuration with 4 fibers (2 fibers per level) in a cross position, measuring 7.82 MPa.

  • Among the specimens using 90-day C25 concrete, the highest flexural strength value is 13.50 MPa, and 4-fibered (2 fiber-2 level) and straight-position specimens.

  • Within the category of specimens employing 90-day SCC, the specimen featuring the highest flexural strength measurement was attained by the setup with 4 fibers (2 fibers per level) in a cross position, recording a value of 15.64 MPa.

  • Among the C25 concrete specimens kept in sulfate water for 90 days, the highest flexural strength value is 7.15 MPa with whole (2 level) specimen.

  • Flexural strength values of all SCC specimens kept in sulfated water for 90 days are lower than the reference specimen.

  • The deflection capacity in the beams increases in direct proportion to the number of fibers, the fibers induce ductile fracture even in straight or cross positions, and the reference samples experience the most brittle fracture.

It is understood that SCC specimens are more successful. Since no vibration is applied to the SCC, it is thought that the fibers maintain their position and fulfill their functions, while the fiberglass mesh provides better adhesion to the concrete thanks to its mesh structure.

The flexural strength values of the fibrous specimens exposed to sulfated water exhibited significant reductions in both the C25 concrete category and the SCC category. Both the SCC and C25 concrete classes had significant declines in flexural strength values as a result of the fibrous specimens’ exposure to sulfated waters. According to the findings of this study, using waste GFM in concrete will contribute positively effect to the environment while increasing the flexural strength and ductile fracture of the beams in both SCC and C25 concrete samples. In addition, since it is plastic based, it does not pose a corrosion hazard in concrete.

Acknowledgement

Thanks to Bilecik Şeyh Edebali University, which enables experiments to be carried out using Civil Engineering Building Materials Laboratories.

  1. Funding information: There is no funding for this article.

  2. Author contributions: The author confirms sole responsibility for the following: study conception and design, data collection, analysis and interpretation of results, and article preparation.

  3. Conflict of interest: The author declares no conflict of interest.

  4. Ethical approval: The conducted research is not related to either human or animal use.

  5. Data availability statement: Derived data supporting the findings of this study are available from the corresponding author on request.

References

[1] Rafiq Bhat A, Vikram A. Performance of concrete with polypropylene fibre and polyvinyl chloride fibre. Mater Today Proc. 2023. 10.1016/j.matpr.2023.03.104.Search in Google Scholar

[2] Hussain I, Ali B, Akhtar T, Jameel MS, Raza SS. Comparison of mechanical properties of concrete and design thickness of pavement with different types of fiber-reinforcements (steel, glass, and polypropylene). Case Stud Constr Mater. 2020;13:e00429. 10.1016/j.cscm.2020.e00429.Search in Google Scholar

[3] Al-Rousan ET, Khalid HR, Rahman MK. Fresh, mechanical, and durability properties of basalt fiber-reinforced concrete (BFRC): a review. Dev Built Environ. 2023;14(Feb):100155. 10.1016/j.dibe.2023.100155.Search in Google Scholar

[4] Sinkhonde D, Ocharo R, Odhiambo W, Nyiro J. Ductility performance of reinforced rubberised concrete beams incorporating burnt clay powder. Heliyon. 2021;7(Aug):e08310. 10.1016/j.heliyon.2021.e08310.Search in Google Scholar PubMed PubMed Central

[5] Khan MS, Fuzail Hashmi A, Shariq M, Ibrahim SM. Effects of incorporating fibres on mechanical properties of fibre-reinforced concrete: a review. Mater Today Proc. 2023. 10.1016/j.matpr.2023.05.106.Search in Google Scholar

[6] Garikapati KP, Sadeghian P. Mechanical behavior of flax-lime concrete blocks made of waste flax shives and lime binder reinforced with jute fabric. J Build Eng. 2020;29(Jan):101187. 10.1016/j.jobe.2020.101187.Search in Google Scholar

[7] Rahman SS, Siddiqua S, Cherian C. Sustainable applications of textile waste fiber in the construction and geotechnical industries: a retrospect. Clean Eng Technol. 2022;6(Jan):100420. 10.1016/j.clet.2022.100420.Search in Google Scholar

[8] Amadei AM, Sanyé-Mengual E, Sala S. Modeling the EU plastic footprint: Exploring data sources and littering potential. Resour Conserv Recycl. 2022;178(Dec 2021):106086.10.1016/j.resconrec.2021.106086Search in Google Scholar

[9] Selvapriya R, Arun Kumar VS, Keruthiga V, Mahesh Kumar A, Bharath G. Experimental investigation on the behaviour of flexural strengthening of beams using carbon fibre reinforced polymer sheet. Mater Today Proc. 2022;68:1673–9. 10.1016/j.matpr.2022.08.130.Search in Google Scholar

[10] Gopinath M, Abimaniu P, Dharsan Rishi C, Pravinkumar K, Tejeshwar PG. Experimental investigation on waste plastic fibre concrete with partial replacement of coarse aggregate by recycled coarse aggregate. Mater Today Proc. 2023. 10.1016/j.matpr.2023.04.573.Search in Google Scholar

[11] Qin Y, Zhang X, Chai J, Xu Z, Li S. Experimental study of compressive behavior of polypropylene-fiber- reinforced and polypropylene-fiber-fabric-reinforced concrete. Constr Build Mater. 2019;194:216–25. 10.1016/j.conbuildmat.2018.11.042.Search in Google Scholar

[12] Qin Y, Zhang X, Chai J. Damage performance and compressive behavior of early-age green concrete with recycled nylon fiber fabric under an axial load. Constr Build Mater. 2019;209:105–14. 10.1016/j.conbuildmat.2019.03.094.Search in Google Scholar

[13] Özkılıç YO, Beskopylny AN, Stel’makh SA, Shcherban’ EM, Mailyan LR, Meskhi B, et al. Lightweight expanded-clay fiber concrete with improved characteristics reinforced with short natural fibers. Case Stud Constr Mater. 2023;19(Aug):e02367.10.1016/j.cscm.2023.e02367Search in Google Scholar

[14] Thienel KC, Haller T, Beuntner N. Lightweight concrete-from basics to innovations. Materials (Basel). 2020;13(5):1120.10.3390/ma13051120Search in Google Scholar PubMed PubMed Central

[15] Nguyen W, Martinez DM, Jen G, Duncan JF, Ostertag P. Interaction between global warming potential, durability, and structural properties of fiber-reinforced concrete with high waste materials inclusion. Resour Conserv Recycl. 2021;169(Feb):105453. 10.1016/j.resconrec.2021.105453.Search in Google Scholar

[16] Seddik M, Bencheikh M. Properties of concrete reinforced with different kinds of industrial waste fibre materials. Constr Build Mater. 2009;23(10):3196–205. 10.1016/j.conbuildmat.2009.06.017.Search in Google Scholar

[17] Torkaman J, Ashori A, Sadr A. Using wood fiber waste, rice husk ash, and limestone powder waste as cement replacement materials for lightweight concrete blocks. Constr Build Mater. 2014;50:432–6. 10.1016/j.conbuildmat.2013.09.044.Search in Google Scholar

[18] Ray S, Rahman M, Haque M, Hasan MW, Alam MM. Performance evaluation of SVM and GBM in predicting compressive and splitting tensile strength of concrete prepared with ceramic waste and nylon fiber. J King Saud Univ - Eng Sci. 2021;35(2):92–100. 10.1016/j.jksues.2021.02.009.Search in Google Scholar

[19] Akhtar T, Ali B, Ben N, Kurda R, Rizwan M, Mohsin M, et al. Experimental investigation of eco-friendly high strength fiber-reinforced concrete developed with combined incorporation of tyre-steel fiber and fly ash. Constr Build Mater. 2022;314(PA):125626. 10.1016/j.conbuildmat.2021.125626.Search in Google Scholar

[20] Qasim S, Salah M, Al-abbas BH. Mechanical and structural properties of waste rope fibers-based concrete: an experimental study. Case Stud Constr Mater. 2022;16(Nov 2021):e00964. 10.1016/j.cscm.2022.e00964.Search in Google Scholar

[21] Preferred Fiber & Materials Market Report 2020 Welcome to the 2020 Preferred Fiber & Materials Market Report; 2020.Search in Google Scholar

[22] Akbari H, Erickson B, Nanni A. Flexural analysis and design of FRCM-strengthened RC beams. Constr Build Mater. 2020;244:118371. 10.1016/j.conbuildmat.2020.118371.Search in Google Scholar

[23] Grande E, Milani G. Numerical simulation of the tensile behavior of FRCM strengthening systems. Compos Part B. 2020;189(Nov 2019):107886. 10.1016/j.compositesb.2020.107886.Search in Google Scholar

[24] Nerilli F, Marfia S, Sacco E. Micromechanical modeling of the constitutive response of FRCM composites. Constr Build Mater. 2020;236:117539. 10.1016/j.conbuildmat.2019.117539.Search in Google Scholar

[25] Faleschini F, Angelo M, Hofer L, Pellegrino C. Experimental behavior of reinforced concrete columns confined with carbon-FRCM composites. Constr Build Mater. 2020;243:118296. 10.1016/j.conbuildmat.2020.118296.Search in Google Scholar

[26] Raoof SM, Koutas LN, Bournas DA. Bond between textile-reinforced mortar (TRM) and concrete substrates: experimental investigation. Compos Part B. 2016;98:350–61. 10.1016/j.compositesb.2016.05.041.Search in Google Scholar

[27] Tetta ZC, Koutas LN, Bournas DA. Textile-reinforced mortar (TRM) versus fiber-reinforced polymers (FRP) in shear strengthening of concrete beams. Compos Part B. 2015;77:338–48. 10.1016/j.compositesb.2015.03.055.Search in Google Scholar

[28] Vieira ADA, Triantafyllou SP, Bournas DA. Strengthening of RC frame subassemblies against progressive collapse using TRM and NSM reinforcement. Eng Struct. 2020;207(Jan):110002. 10.1016/j.engstruct.2019.110002.Search in Google Scholar

[29] Bertolesi E, Buitrago M, Giordano E, Calderón PA, Moragues JJ, Clementi F, et al. Effectiveness of textile reinforced mortar ( TRM) materials in preventing seismic-induced damage in a U-shaped masonry structure submitted to pseudo-dynamic excitations. Constr Build Mater. 2020;248:118532. 10.1016/j.conbuildmat.2020.118532.Search in Google Scholar

[30] Wang X, Lam CC, Iu VP. Comparison of different types of TRM composites for strengthening masonry panels. Constr Build Mater. 2019;219:184–94. 10.1016/j.conbuildmat.2019.05.179.Search in Google Scholar

[31] Donnini J, Spagnuolo S, Corinaldesi V. A comparison between the use of FRP, FRCM and HPM for concrete confinement. Compos Part B. 2019;160(Dec 2018):586–94. 10.1016/j.compositesb.2018.12.111.Search in Google Scholar

[32] Sadrolodabaee P, Claramunt J, Ardanuy M, De A. Case Studies in Construction Materials Mechanical and durability characterization of a new textile waste micro fiber reinforced cement composite for building applications. Case Stud Constr Mater. 2021;14:e00492. 10.1016/j.cscm.2021.e00492.Search in Google Scholar

[33] Bencardino F, Carloni C, Condello A, Focacci F, Napoli A, Realfonzo R. Flexural behaviour of RC members strengthened with FRCM: State-of-the-art and predictive formulas. Compos Part B. 2018;148(Apr):132–48. 10.1016/j.compositesb.2018.04.051.Search in Google Scholar

[34] Ababneh AN, Al-rousan RZ, Ghaith IMN. Experimental study on anchoring of FRP-strengthened concrete beams. Structures. 2020;23(July 2019):26–33. 10.1016/j.istruc.2019.09.018.Search in Google Scholar

[35] Zhu D, Peled A, Mobasher B. Dynamic tensile testing of fabric – cement composites. Constr Build Mater. 2011;25(1):385–95. 10.1016/j.conbuildmat.2010.06.014.Search in Google Scholar

[36] Akand L, Yang M, Wang X. Effectiveness of chemical treatment on polypropylene fibers as reinforcement in pervious concrete. Constr Build Mater. 2018;163:32–9. 10.1016/j.conbuildmat.2017.12.068.Search in Google Scholar

[37] Bernat-maso E, Gil L, Mercedes L, Escrig C. Mechanical properties of pre-stressed fabric-reinforced cementitious matrix composite (PFRCM). Constr Build Mater. 2018;191:228–41. 10.1016/j.conbuildmat.2018.09.210.Search in Google Scholar

[38] Du Y, Zhang X, Zhou F, Zhu D, Zhang M, Pan W. Flexural behavior of basalt textile-reinforced concrete. Constr Build Mater. 2018;183:7–21. 10.1016/j.conbuildmat.2018.06.165.Search in Google Scholar

[39] Kumar R, Babu TSR, Venkatesan G, Padhi SN, Lukesh J, Kumar VR. Investigation of fiber reinforced concrete – Energy absorption capacity with steel and polymeric fibers. Mater Today Proc. 2023 Aug. 10.1016/j.matpr.2023.08.076.Search in Google Scholar

[40] Safiddine S, Amokrane K, Debieb F, Soualhi H, Benabed B, Kadri EH. How quarry waste limestone filler affects the rheological behavior of cement-based materials. Appl Rheol. 2021;31(1):63–75.10.1515/arh-2020-0118Search in Google Scholar

[41] Ren G, Yao B, Ren M, Gao X. Utilization of natural sisal fibers to manufacture eco-friendly ultra-high performance concrete with low autogenous shrinkage. J Clean Prod. 2022;332(Dec 2021):130105. 10.1016/j.jclepro.2021.130105.Search in Google Scholar

[42] Cao Y, Zandi Y, Rahimi A, Wu Y, Fu L, Wang Q. A new intelligence fuzzy-based hybrid metaheuristic algorithm for analyzing the application of tea waste in concrete as natural fiber. Comput Electron Agric. 2021;190(Aug):106420.10.1016/j.compag.2021.106420Search in Google Scholar

[43] Ahmad W, Farooq SH, Usman M, Khan M, Ahmad A, Aslam F, et al. Effect of coconut fiber length and content on properties of high strength concrete. Materials (Basel). 2020;13(5):1075.10.3390/ma13051075Search in Google Scholar PubMed PubMed Central

[44] Solahuddin BA. A critical review on experimental investigation and finite element analysis on structural performance of kenaf fibre reinforced concrete. Structures. 2022;35(Nov 2021):1030–61. 10.1016/j.istruc.2021.11.056.Search in Google Scholar

[45] Ouari N, Kaci A, Tahakourt A, Chaouche M. Rheological behaviour of fibre suspensions in non-Newtonian fluids. Appl Rheol. 2011;21(5):1–10.Search in Google Scholar

[46] Varghese A, Unnikrishnan S. Mechanical strength of coconut fiber reinforced concrete. Mater Today Proc. 2023. 10.1016/j.matpr.2023.05.637.Search in Google Scholar

[47] Wang W, Zhang Y, Mo Z, Chouw N, Jayaraman K, Xu ZD. A critical review on the properties of natural fibre reinforced concrete composites subjected to impact loading. J Build Eng. 2023;77(Aug):107497. 10.1016/j.jobe.2023.107497.Search in Google Scholar

[48] Lee S, Ryu S, Won J. Relationship between the rheology and flowability of self-compacting structural synthetic fibre-reinforced cementitious composites. Compos Struct. 2021;267(Mar):113862. 10.1016/j.compstruct.2021.113862.Search in Google Scholar

[49] Sanjeev J, Nitesh KJNS. Study on the effect of steel and glass fibers on fresh and hardened properties of vibrated concrete and self-compacting concrete. Mater Today Proc. 2020;27:1559–68. 10.1016/j.matpr.2020.03.208.Search in Google Scholar

[50] Magbool HM, Zeyad AM. The effect of various steel fibers and volcanic pumice powder on fracture characteristics of Self-Compacting concrete. Constr Build Mater. 2021;312(Nov):125444. 10.1016/j.conbuildmat.2021.125444.Search in Google Scholar

[51] Kotwal S, Singh H, Kumar R. Experimental investigation of Steel Fibre reinforced Self Compacting Concrete (SCC) using recycled aggregates as partial replacement of coarse aggregates. Mater Today Proc. 2022;48:1032–7. 10.1016/j.matpr.2021.06.436 Search in Google Scholar

[52] Alani AM, Beckett D. Mechanical properties of a large scale synthetic fibre reinforced concrete ground slab. Constr Build Mater. 2013;41:335–44. 10.1016/j.conbuildmat.2012.11.043.Search in Google Scholar

[53] Orouji M, Mehdi S, Najaf E. Effect of glass powder & polypropylene fibers on compressive and flexural strengths, toughness and ductility of concrete: An environmental approach. Structures. 2021;33(Jul):4616–28. 10.1016/j.istruc.2021.07.048.Search in Google Scholar

[54] Li Z, Zhu H, Zhen X, Wen C, Chen G. Effects of steel fi ber on the fl exural behavior and ductility of concrete beams reinforced with BFRP rebars under repeated loading. Compos Struct. 2021;270(Mar):114072. 10.1016/j.compstruct.2021.114072.Search in Google Scholar

[55] Shi F, Pham TM, Hao H, Hao Y. Post-cracking behaviour of basalt and macro polypropylene hybrid fibre reinforced concrete with different compressive strengths. Constr Build Mater. 2020;262:120108. 10.1016/j.conbuildmat.2020.120108.Search in Google Scholar

[56] Devi Keerthika Esakki AK, Karan Aakash Dev S, Gomathy T, Chella Gifta C. Influence of adding steel – glass – polypropylene fibers on the strength and flexural behaviour of hybrid fiber reinforced concrete. Mater Today Proc. 2023. 10.1016/j.matpr.2023.05.055.Search in Google Scholar

[57] Ferrara L, Bamonte P, Caverzan A, Musa A, Sanal I. A comprehensive methodology to test the performance of steel fibre reinforced self-compacting concrete (SFR-SCC). Constr Build Mater. 2012;37:406–24. 10.1016/j.conbuildmat.2012.07.057.Search in Google Scholar

Received: 2023-08-14
Revised: 2023-09-01
Accepted: 2023-09-18
Published Online: 2023-10-10

© 2023 the author(s), published by De Gruyter

This work is licensed under the Creative Commons Attribution 4.0 International License.

Downloaded on 4.5.2024 from https://www.degruyter.com/document/doi/10.1515/arh-2023-0109/html
Scroll to top button